Signal catalog
| Signal source | Detected pattern | Automatic action |
|---|---|---|
| Sensibo (temp / rH / setpoint) | Setpoint not reached for more than 30 min under a stable outdoor load | Diagnosis candidate, dry-run recommendation, ticket in Inventory |
| Shelly (P, kWh) | Consumption drifts more than 15% against baseline in the same operating mode | Anomaly with a physical explanation, candidate for maintenance |
| Home Assistant history | Hot-water meter shows a systematic -3% against Shelly | Calibration notice, correction factor 1.031 active, noted in the EvidenceRecord |
| Asset battery | ≤ 15% warning · ≤ 10% critical · 0% offline | Staged alerts with duplicate suppression and notification audit |
| Maintenance plan | Grundfos ALPHA1 25-60 / Vaillant aroSTOR VWL BM 270/5: 12-month cycle | Automatic service-plan ticket 30 / 14 / 7 days before due date |
| CAD ⇔ as-built model | Missing geometry or deviating zones | MISSING_GEOMETRY_AREA reported, no substitute value, engineering review |
| Temperature watchdog | Room below 24 °C with rH above the target band | Blocks deeper cooling; recommends dry mode / ventilation |
| Emergency stop endpoint | Critical anomaly with a safety implication | Emergency route triggers immediate HVAC shutdown outside the dry-run gate |